BBA000100100 Battery balancer Victron Energy
- Brand: Victron Energy
- Availability: In Stock
- Product Code: BBA000100100
- Bluetooth
- DC Input/Output , V
- Input voltage, AC (DC)
- Output current, А
- Output power, W
The problem: the service life of an expensive
battery bank can be substantially shortened due to state of charge unbalance
One battery
with a slightly higher internal leakage current in a 24V or 48V bank of several
series/parallel connected batteries will cause undercharge of that battery and
parallel connected batteries, and overcharge of the series connected batteries.
Moreover, when new cells or batteries are connected in series, they should all
have the same initial state of charge. Small differences will be ironed out
during absorption or equalize charging, but large differences will result in
damage due to excessive gassing (caused by overcharging) of the batteries with
the higher initial state of charge and sulphation (caused by undercharging) of
the batteries with the lower initial state of charge.
The Solution: battery balancing
The Battery
Balancer equalizes the state of charge of two series connected 12V batteries,
or of several parallel strings of series connected batteries.
When the
charge voltage of a 24V battery system increases to more than 27,3V, the Battery
Balancer will turn on and compare the voltage over the two series connected
batteries. The Battery Balancer will draw a current of up to 0,7A from the
battery (or parallel connected batteries) with the highest voltage. The
resulting charge current differential will ensure that all batteries will
converge to the same state of charge.
If needed,
several balancers can be paralleled.
A 48V
battery bank can be balanced with three Battery Balancers.
LED indicators
Green: on (battery voltage > 27,3V)
Orange: lower battery leg active (deviation >
0,1V)
Orange: upper battery leg active (deviation >
0,1V)
Red: alarm (deviation > 0,2V). Remains on until
the deviation has reduced to less than 0,14V, or until system voltage drops to
less than 26,6V.
Alarm relay
Normally
open. The alarm relay closes when the red LED switches on and opens when the
red LED switches off.
Alarm reset
Two
terminals are available to connect a push button. Interconnecting the two
terminals resets the relay.
The reset
condition will remain active until the alarm is over. Thereafter the relay will
close again when a new alarm occurs.
Even more insight and control with the midpoint
monitoring function of the BMV-702
Battery
Monitor The BMV-702 measures the midpoint of a string of cells or batteries. It
displays the deviation from the ideal midpoint in volts or percent. Separate
deviation percentages can be set to trigger a visual/audible alarm and to close
a potential free relay contact for remote alarm purposes.
Please see
the manual of the BMV-702 for more information about battery balancing.